PR electronics 9106B Intrinsically safe grid

- +
Custom Settings Company Homepage More Products

The quotes are provided by Several Partner Companies

  • Prices: Request for a Quote for Further Details
  • Model : 9106B
  • Category: Intrinsically Safe Grid
  • Brand : PR electronics
  • Delivery Time: Request for a Quote for Further Details
  • Manufacturer: PR electronics

Products

characteristic.

  • 9106B is a 1- or 2-channel isolated 1:1 repeater barrier for intrinsic safety applications.
  • The device supplies 2-wire SMART transmitters and can also be used for 2-wire SMART current sources. HART® & BRAIN protocols are supported and are transferred bi-directionally.
  • 9106B can be mounted in the safe area or in zone 2 / Cl. 1,div. 2 and receive signals from zone 0,1,2 and zone 20,21,22 inc / Class I/II/III,Div. 1,Gr. A-G.
  • The PR 4501 displays the process value for each channel and can be used to define high and low limits for detection of loop current level. If these limits are exceeded,the status relay will activate.
  • In the 1-channel version the status relay can be used as a simple limit switch.
  • I.S. splitter application - 1 input and 2 outputs.
  • In the dual channel version the 9106B can be implemented in a SIL3 loop.
  • The PR 4501 detachable display and the green and red front LEDs indicate operation status for each channel.
  • A tag number can be defined for each channel.
  • Monitoring of error events and cable breakage on input via the individual status relay and/or a collective electronic signal via the power rail.
  • High galvanic isolation of 2.6 kVAC.
  • Fast response time<5 ms
  • High accuracy better than 0.1%.
  • 2-wire transmitter supply >16 V.
  • PR9106B is recommended as Ex / I.S. safety barrier for 5335D,5337D,6335D and 6337D.
  • The devices can be mounted vertically or horizontally without distance between neighbouring units.

"Application","Advanced features","Technical characteristics","Mounting"

Product Specifications

Parameter Value Parameter Value
Safety barrier type Galvanic Isolator Working temperature -4 to 140 F (-20 to 60 C)
ATEX certification DEKRA 11ATEX0244 X The depth of the 4.09 inch (104 mm)
Environmental or explosion protection level IP20 FM license 0003044327-C
highly 4.29 inch (109 mm) ISC Compatible 1000 milliamps
Installation plan Din Rail Mounted other DEK 11.0084X
Product category Intrinsic Safety Barriers UL certification UL 61010-1
VOC compliance 32 volts The weight of the 0.5513 lbs (0.2500 kg)
The width of the 0.9252 inch (23.5 mm)