Hebei OSU Electronics Air temperature and humidity, carbon dioxide three-parameter sensor Temperature and humidity sensor

- +
Custom Settings Company Homepage More Products

The quotes are provided by Several Partner Companies

  • Prices: Request for a Quote for Further Details
  • Model : Air temperature, humidity and carbon dioxide three-parameter sensor
  • Category: Temperature Sensors
  • Brand : Hebei North Speed ​​Electronics
  • Delivery Time: Request for a Quote for Further Details
  • Manufacturer: Hebei North Speed ​​Electronics

Products


1


product description

The air temperature,humidity and carbon dioxide sensors adopt imported digital temperature and humidity sensors andNon-dispersive infrared (NDIR) principle carbon dioxideThe sensor has been carefully calibrated during production,and the calibration data is stored in the internal memory. The sensor has digital output and is fully interconvertible,and does not require complex verification.Calibration process,excellent measurement accuracy,linearity,repeatability,interconvertibility,consistency,etc.,designed with a temperature compensation circuit,can be used under different ambient temperatures,and is suitable for various fields that require the measurement of temperature,humidity and carbon dioxide concentration.


2


Features

1Using imported temperature and humidity and non-dispersive infrared (NDIR) Principle carbon dioxide sensor,accurate and reliable

2High cost performance,wide voltage design

3Full range temperature and humidity compensation,wide measuring range,optional measuring range

4Flexible installation and easy to use

5Small size,light weight,anti-vibration


3

Scope of application

It is widely used in weather stations,greenhouses,environmental monitoring stations,medicine and health,purification workshops,precision laboratories,fermentation tanks,breeding workshops and other fields that need to monitor air temperature,humidity and carbon dioxide concentration.


4


Product information

Measured parameter: air temperatureAir humidityThree parameters of carbon dioxide concentration

Units of measurement:%RHppm

Measuring range: air temperature:3070

Air humidity:099.99%RH

Carbon dioxide concentration:02000500010000ppm(Other ranges optional)

Resolution:0.10.1%RH1ppm

measurement accuracy:±0.2±3%RH±20ppm

Operating temperature:-2070

output signal:RS485(standardModbus-RTUprotocol,Device default address:01

Operating Voltage:524V DC

Working current:

Stabilization time: after power on3min

Response time:<1Second

Cable specifications:2rice4Wire system (RS485) (cable length optional)


5

productSpecification

6

Instructions

Air temperature,humidity and carbon dioxide sensors can be connected to various data collectors with differential input,data acquisition cards,remote data acquisition modules and other equipmentWiring instructions are as shown below


Note: Be careful when wiring. If the power supply voltage is too high or the polarity is reversed,it will cause the sensor to malfunction.foreversexual damage


7

Data conversion method

RS485signal,standardModbus-RTUprotocol

Baud rate:9600;Check bit: none;Data bit:8;Stop bit:1

7.1address

For example: the address to1The sensor address is changed to2,hostSlave machine

original address

function code

Start register high

Start register low

Starting address high

Starting address is low

CRC16Low

CRC16high

0X01

0X06

0X00

0X30

0X00

0X02

0X08

0X04

If the sensor receives correctly,the data will be returned along the original path.

Remark:If you forget the sensorOriginalAddress,you can use the broadcast address0XFEreplace,use0XFEThe master can only connect one slave,and the return address is still the original address,which can be used as an address query method.

7.2Query data

Query the sensor (address is1) data (air temperature,humidity,carbon dioxide),hostSlave machine

address

function code

Starting register address high

Starting register address low

Register length is high

Register length is low

CRC16Low

CRC16high

0X01

0X03

0X00

0X00

0X00

0X03

0X05

0XCB

If the sensor receives correctly,the following data will be returned,and the slaveHost

address

0X01


function code

0X03


Data length

0X06


register0High data

0XFF

Air temperature: -3.5℃

register0data low

0XDD

register1High data

0X01

Air humidity:35.6 %RH

register1data low

0X64

register2High data

0X0E

Carbon dioxide concentration:3682ppm

register2data low

0X62

CRC16Low

0X08


CRC16high

0X33


8

Precautions for use

1When receiving the product,please check whether the packaging is intact and check whether the sensor model and specifications match the product you purchased.

2The installation location should be away from chemically corrosive environments

3Sensors and wires should be kept away from high-voltage electricity,heat sources,etc.

4The sensor is a precision instrument and should be stored in a dry,ventilated and room-temperature indoor environment.

5The sensor is a precision device. Users should not disassemble it by themselves when using it to avoid product damage.


9

Product warranty

The warranty period of this product is one year. Within twelve months from the date of shipment,our company will be responsible for free repair or replacement of any failure caused by sensor quality problems (non-human damage). After the warranty period,only the cost will be charged.