Hanwei Technology KB100 Industrial and Commercial Gas Safety Monitoring
- Prices: Request for a Quote for Further Details
- Model : KB100
- Category: Fire Alarm Control Panel
- Brand : Harvest technology
- Delivery Time: Request for a Quote for Further Details
- Manufacturer: Han Wei
Products
Product advantages:
4-way compact model;
Full LCD human-machine interface,status indication is clearly visible;
New generation bus;
One channel has four bus detector inputs and one fire bus supports data upload.
Features:
Installation method:wall hanging
main power:AC 220V±33V 50Hz±5Hz
power:≤10W (exc external detector)
Alarm method:Sound (sound pressure level above 65dB at a distance of 1 meter) and light alarm
Operating temperature:-10℃~50℃
Product Details:
The KB100 gas alarm controller can be combined with the Group's and GT-CXE series detectors to form an industrial gas intelligent control system,which is used to monitor and alarm gas concentrations at industrial sites. When the air contains the gas to be measured or the liquid volatilizes,the detector generates an electrical signal proportional to the concentration of the gas to be measured in the air. This signal is transmitted to the controller,and the controller displays the concentration of the gas to be measured after processing. When the measured gas concentration reaches or exceeds the set value,the controller will send out audible and visual alarm signals,output relevant control signals,and activate corresponding control devices to avoid major accidents.
main application:
It is combined with an alarm to form a combustible gas alarm control system,which is suitable for nine small places such as industrial and commercial small restaurants,snack bars,barber shops,bathrooms,small hospitals,and environments where gas may leak such as shopping malls and underground comprehensive pipe corridors.
Technical indicators:
Installation method | wall hanging |
main power | AC 220V±33V 50Hz±5Hz |
backup power | DC 24V±3V rechargeable lead-acid battery |
power rate | ≤10W (exc external detector) |
Display method | Dot matrix LCD and status indicators |
signal input | 1 POWER BUS bus can be connected to 4 detectors |
Data upload | 1 channel (RS485),supports wireless |
Alarm Output | 2-way programmable relay,contact capacity ≤5A |
Alarm mode | Sound (sound pressure level above 65dB at a distance of 1 meter) and light alarm |
Operating temperature | -10℃~50℃ |
Working humidity | ≤95%RH (non-condensing) |
Display method | Dot matrix LCD screen and status indicator lights |
Product Size | 260mm×200mm×62mm |