Hanwei Technology KB6000Ⅲ Gas Alarm Controller

- +
Custom Settings Company Homepage More Products

The quotes are provided by Several Partner Companies

  • Prices: Request for a Quote for Further Details
  • Model : KB6000Ⅲ
  • Category: Alarm
  • Brand : Harvest technology
  • Delivery Time: Request for a Quote for Further Details
  • Manufacturer: Han Wei

Products

Features:

  • model:KB6000Ⅲ

  • form:Wall-mounted

  • Way of working:RS485 bus system

  • Response time:≤30s

  • Number of mounted detectors:≤30 pieces


Product Details:

KB6000Ⅲ gas alarm controller,Modbus master station (such as PLC,PC,etc.) and the company's TC100Ⅱ and other bus-type gas detectors form an industrial gas alarm control system. The KB6000Ⅲ gas alarm controller communicates with bus-type gas detectors such as TC100Ⅱ using the communication protocol provided by the company,and communicates with the Modbus master station. Its physical interface uses the RS485 interface,and the communication protocol uses the MODBUS RTU protocol.


Product advantages:

Automatic search at startup

Up to 30 monitoring points,multi-point control at the same time

Simulate menu,easy to operate

Automatically realize seamless switching between main and backup power

External devices can be started via the controller

Intelligent system facilitates online zero calibration and relay passive output

Optional 1 RS485 (MODBUS) signal output to communicate with the host computer and can be connected to large safety systems such as DCS,PLC and so on.

The host computer has an embedded microprocessor and is equipped with rich software functions to complete detector signal sampling,real-time data calculation,system fault detection,power management,key sc,display driver,alarm display,alarm peripheral driver and other functions.

When the preset logical relationship is met,the connected external device can act on its own

Intelligent management of detectors that detect different gas types,different ranges,and different data units


main application:

This product can monitor a variety of gases such as flammable gases,toxic gases,and oxygen when used in conjunction with appropriate detectors.


Technical indicators:

projectTechnical Parameters
modelKB6000Ⅲ
formWall-mounted
Way of workingRS485 bus system
Response time≤30s
Self-test functionhave
Number of mounted detectors≤30 pieces
Alarm modeSound (sound pressure level at a distance of 1 meter is above 65dB and below 115dB),light alarm
Instruction methodIndicator lights indicate detector status


The digital tube displays the alarm concentration or alarm detector number

Different alarm sounds indicate alarm and fault status

alarm record1000 items
Contact outputPassive contact capacity 2A/AC220V,(some models contain active nodes)
power supplyMain power supply: AC220V±15% 50Hz±1%


Backup power supply: DC24V rechargeable lead-acid battery

power rate≤15W
Protection levelIP54
showLED digital + analog
ambient temperature-10℃~50℃
Relative humidity<95% (no condensation)
Dimensionsl×b×h,mm:390×280×116.2 (with mounting base plate)