Fluid Components Intl. (FCI) MT100M Flow Meter

- +
Custom Settings Company Homepage More Products

The quotes are provided by Several Partner Companies

  • Prices: Request for a Quote for Further Details
  • Model : MT100M
  • Category: Flow Meters
  • Brand : Fluid Components Intl. (FCI)
  • Delivery Time: Request for a Quote for Further Details
  • Manufacturer: Fluid Components Intl.FCI

Products

The MT100 Series is an insertion-type multi-point thermal flow meter designed for large diameter ducts (such as chimneys and flues) and large rectangular ducts (such as air inlets and HVAC). The application of these large pipes is difficult for ordinary flow meters because the distorted flow profile and lack of straight pipe sections can lead to inaccurate and non-repeatable flow measurements. FCI's MT100 places up to eight (8) flow sensing points in the flow of water and averages them,resulting in highly accurate and repeatable flow measurements. Unlike other large pipe flow meters,the MT100 has no moving parts or orifice plates to clog or clog. The plug-in design on the same plane makes it easy to install and less expensive. There are solutions available for use in fluids with temperatures up to 850°F 454°C. The electronics feature dual 4-20mA outputs with HART and Modbus,and optional Foundation fieldbus or PROFIBUS,a state-of-the-art touch-sensitive large digital + graphic LCD display,data logging,calibration self-test and easy wiring. The transmitter housing is made of the highest quality corrosion-resistant stainless steel. The MT100 series multi-point thermal flow meter is the solution for large diameter pipe and duct applications.

Characteristics

  • Combustion air
  • Flue gas flow
  • Primary air,secondary air and over-fire air flow
  • Preheater air Flow
  • Boiler inlet flow
  • Fume gas flow
  • Emission flow monitoring/reporting (cems)
  • HVAC controls
  • Exhaust gas flow
  • Boiler air supply flow

Product Specifications

Parameter Value Parameter Value
precision 2 ±% work pressure 0.0 to 100 psi (0.0 to 70.38 m H2O)
Medium temperature 850 F (454 C) Measuring the dielectric Gas
Characteristics of the Multi-insertion; Programmable The electrical output Current; Switch; Voltage
The interface options Serial/Digital; Network/Fieldbus Working temperature -40 to 150 F (-40 to 66 C)
The terminal fittings MNPT or DIN50;Other Pipe diameter 2.00 inch (50.8 mm)
The instrument type Mass Flow Meter The installation Insertion
The front panel interface Digital Front Panel Audit certification ATEX; NEMA, ISO/IEC, NIST, CRN, US EPA CEMS(Optional)
Product category Flow Meters