Shenwei Electronics SW521PPRO infrared SF6 gas sensor

- +
Custom Settings Company Homepage More Products

The quotes are provided by Several Partner Companies

  • Prices: Request for a Quote for Further Details
  • Model : SW521PPRO
  • Category: Gas Transducer
  • Brand : Shanghai Shenwei Electronics
  • Delivery Time: Request for a Quote for Further Details
  • Manufacturer: Shanghai Shenwei Electronics

Products

SW521PPRO is an SF6 gas sensor using the NDIR infrared absorption detection principle. It is widely used in the power industry, especially in power equipment, such as high-voltage circuit breakers, transformers, mutual inductors, capacitors, arresters, fuses, etc. The significance of the SF6 gas sensor is to promptly detect the concentration of SF6 in the current environment in order to determine whether a leak has occurred and to avoid the decomposition of SF6 gas in the industrial environment to produce toxic gases such as SF4 and other serious consequences. Compared with similar products, this module uses a gold-plated cavity, which has superior performance, good stability and high precision. The measurement range is 0-5000ppm; the resolution can reach 1ppm. The output modes include RS485 output, UART output, analog voltage output, and analog current output. 11 to 30 volt power supply, structure size (mm): 80X43X31.

Specifications

SW521PPRO is an SF6 gas sensor using the NDIR infrared absorption detection principle. It is widely used in the power industry, especially in power equipment, such as high-voltage circuit breakers, transformers, mutual inductors, capacitors, arresters, fuses, etc. The significance of the SF6 gas sensor is to promptly detect the concentration of SF6 in the current environment in order to determine whether a leak has occurred and to avoid the decomposition of SF6 gas in the industrial environment to produce toxic gases such as SF4 and other serious consequences.
Compared with similar products, this module uses a gold-plated cavity, which has superior performance, good stability and high precision. The measurement range is 0-5000ppm; the resolution can reach 1ppm. The output modes include RS485 output, UART output, analog voltage output, and analog current output. 11 to 30 volt power supply, structure size (mm): 80X43X31.


working conditions

describesymbolnumerical valueunit
Storage temperature Tstg -20 to 80 °C
Operating temperature TA -20 to +60 °C
Working humidity HA0 to 90 no condensation %RH
work pressure PA 0.8 to 1.2 atm

Electrical characteristics

describesymbolsmallesttypicalmaximumunit
powered by Vs 11 12 30 V
Maximum working current Imax 100 120 150 mA


performanceginsengnumber

describetypicalunit
Detection range (can be customized) 1000 ppm
measurement accuracy±5ppm or ±5% true value, whichever is greater ppm
T90pump suction 5Second
diffusion 30Second
Repeatabilityzero point <±50 ppm
50% FS<±5% of measured value
life 10Year


Product Specifications

Parameter Value Parameter Value
precision 5% Monitoring gas quantity A single gas
Detection technology NDIR Response Time 30 seconds
Characteristics of the Sampling pump The electrical output RS485;
Working temperature -20 to 60 C Working humidity 0 to 90 %
Measuring type The concentration of